Environment   Protection   Industrial Permit   Outfalls   Feature 1

Outfall 001 for the TA-3-22 Power Plant

Description: The discharge of about 300,000 gallons of treated water per day from Outfall 001 creates a continuous flowing perennial reach in upper Sandia Canyon and supports a 3-acre wetland. Water meets all regulatory standards. Most of the water comes from the Co-Generating Power and Steam Plant, which provides heating to buildings at TA-3 in addition to steam for process needs and to produce electricity in one 10-megawatt and two 5-megawatt steam turbines/generators.

Permitted Discharge: Cooling towers, boiler blow-down drains, demineralizer backwash, R/O reject, floor and sink drains and treated sanitary re-use

Receiving Stream: Upper Sandia Canyon, Segment Number 20.6.4.126

Constituent Monitoring: Flow, TSS, E Coli, Total Residual Chlorine, Metals, pH, Temperature, PCBs, WET

Monitoring Frequency: Variable 1/week, 1/month, 1/year

Reporting Frequency: Monthly and annual Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 2

Outfall 13S for the TA-46-347 Sanitary Wastewater System (SWWS) Plant

Description: Wastewater from sanitary sewer, other non-radiological drains and storm water from technical areas throughout the Laboratory are treated at the Sanitary Waste Water System Plant. Currently, no water is discharged at Outfall 13s. Treated sanitary effluent is pumped either to Outfall 001, or to the Sanitary Effluent Reclamation Facility (SERF) for tertiary treatment and reuse at the Strategic Computing Complex cooling towers. Outfall 13s is a sampling point after final treatment processes prior to pumping to Outfall 001 or to the SERF.

Permitted Discharge: Treated sanitary wastewater

Receiving Stream: Upper Sandia Canyon in Segment Numbers 20.6.4.126 or Canada Del Buey, Segment Number 20.6.4.128

Constituent Monitoring: Flow, BOD5, TSS, E. Coli, Total Residual Chlorine, pH, PCBs, and WET

Monitoring Frequency: Variable 1/week, 1/month, 1/year

Reporting Frequency: Monthly and annual Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 3

Outfall 051 for the TA-50-1 Radioactive Liquid Waste Treatment Facility (RLWTF)

Description: The Radioactive Liquid Waste Treatment Facility treats low level and transuranic radioactive liquid wastewater. A mechanical evaporator was installed so no water has been discharged at Outfall 015 since November 2010. Should the evaporator be offline, wastewater would then treated and discharged in batches to Mortandad Canyon. Discharged water meets all regulatory standards.

Permitted Discharge: Treated radioactive liquid waste

Receiving Stream: Ephemeral reach of Effluent Canyon, tributary to Mortandad Canyon, Segment Number 20.6.4.128

Constituent Monitoring: Flow, COD, TSS, Total Toxic Organics, Metals, Total residual Chlorine, pH, Perchlorate, PCBs, and WET

Monitoring Frequency: Variable 1/week, 1/month, 1/year

Reporting Frequency: Monthly, quarterly and annual Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 4

Outfall 05A055 for the TA-16-1508 High Explosives Wastewater Treatment Facility (HEWTF)

Description: The High Explosive Wastewater Treatment Facility (HEWTF) treats high explosive contaminated wastewater, storm water, and cooling tower blow-down from various sites in the southeast section of the Laboratory. Since an evaporator is normally used, the HEWTF has not discharged since November 2007. Should this malfunction, high explosives wastewater influent is effectively treated through multiple processes before being discharged into Cañon de Valle.

Permitted Discharge: Treated high explosives wastewater, storm water, and cooling tower blow-down

Receiving Stream: Ephemeral tributary to Canon de Valle, Segment Number 20.6.4.128

Constituent Monitoring: Flow, COD, TSS, Oil & Grease, Total Toxic Organics, TNT, RDX, Perchlorate, pH and WET

Monitoring Frequency: Variable 1/week, 1/month, 1/quarter, 1/year

Reporting Frequency: Monthly, quarterly and annual Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 5

Outfall 03A022 for the TA-3-2274 Sigma Cooling Tower

Description: Water discharged here includes treated cooling tower blow-down water and storm water from roof drains which is then discharged into Mortandad Canyon. Discharged water meets all regulatory standards. Under emergency facility shut down due to a power outage emergency cooling water, which is potable, overflows from the circulating water pump basin directly to this outfall.

Permitted Discharge: Cooling tower blow-down, storm water, emergency cooling water (potable water)

Receiving Stream: Ephemeral reach of Mortandad Canyon, Segment Number 20.6.4.128

Constituent Monitoring: Flow, TSS, Total Residual Chlorine, Phosphorus, Metals, pH and WET

Monitoring Frequency: Variable 1/day, 1/week, 1/quarter, 1/year

Reporting Frequency: Monthly, quarterly and annual Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 6

Outfall 03A181 for the TA-55-6 Cooling Tower

Description: Treated blow-down water from the Plutonium Facility cooling tower is discharged into Mortandad Canyon. Discharged water meets all regulatory standards.

Permitted Discharge: Cooling tower blow-down and other wastewater

Receiving Stream: Ephemeral reach of Mortandad Canyon, Segment Number 20.6.4.128

Constituent Monitoring: Flow, TSS, Total Residual Chlorine, Metals, pH and WET

Monitoring Frequency: Variable 1/day, 1/week, 1/month, 1/quarter, 1/year

Reporting Frequency: Monthly, quarterly and annual Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 7

Outfall 03A027 for the TA-3-285 & 23127 Strategic Computing Complex (SCC) Cooling Towers

Description: The Strategic Computing Center cooling towers use treated effluent from the SERF facility to conserve potable water resources. The cooling tower blow-down consists of circulation water from the potable water system treated to remove minerals and biota and/or treated effluent from SERF. Water which meets all regulatory standards is then discharged into Sandia Canyon.

Permitted Discharge: Cooling tower blow-down and tertiary treated sanitary wastewater from SERF

Receiving Stream: Upper Sandia Canyon, Segment Number 20.6.4.126

Constituent Monitoring: Flow, TSS, E Coli, Total Residual Chlorine, Phosphorus, Metals, pH and WET

Monitoring Frequency: Variable 1/day, 1/week, 1/quarter and 1/year

Reporting Frequency: Monthly, quarterly and annual Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 8

Outfall 03A113 for the TA-53 Low Energy Demonstration Accelerator (LEDA) Cooling Towers

Description: Treated water from cooling tower blow-down and storm water from parking lots and roof drains is discharged into Sandia Canyon. Discharged water meets all regulatory standards.

Permitted Discharge: Cooling tower blow-down, and storm water runoff

Receiving Stream: Ephemeral tributary to Sandia Canyon, Segment Number 20.6.4.128

Constituent Monitoring: Flow, TSS, Total Residual Chlorine, Phosphorous, Metals, pH and WET

Monitoring Frequency: Variable 1/day, 1/week, 1/quarter, 1/year

Reporting Frequency: Monthly, quarterly and annual Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 9

Outfall 03A199 for the TA-3-1837 Laboratory Data Communications Center (LDCC) Cooling Towers

Description: Treated water from cooling towers at Laboratory Data Communications Center computer equipment and systems is discharged into a perennial reach of Sandia Canyon. Discharged water meets all regulatory standards.

Permitted Discharge: Cooling Tower blow-down

Receiving Stream: Ephemeral tributary to Upper Sandia Canyon, Segment Number 20.6.4.126

Constituent Monitoring: Flow, TSS, Total Residual Chlorine, Phosphorous, Metals, pH and WET

Monitoring Frequency: Variable 1/day, 1/week, 1/quarter and 1/year

Reporting Frequency: Monthly, quarterly and annual Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 10

Outfall 03A048 for the TA-53-964 & 979 Los Alamos Neutron Science Center (LANSCE) Cooling Towers

Description: Cooling towers for the Los Alamos Neutron Science Center provide cooling to equipment and systems at the accelerator facility. The treated water discharged into Los Alamos Canyon meets all regulatory standards.

Permitted Discharge: Cooling tower blow-down

Receiving Stream: Ephemeral tributary to Los Alamos Canyon, Segment Number 20.6.4.128

Constituent Monitoring: Flow, TSS, Total Residual Chlorine, Phosphorous, Metals, pH and WET

Monitoring Frequency: Variable 1/day, 1/week, 1/month, 1/quarter

Reporting Frequency: Monthly and quarterly Discharge Monitoring Reports (DMRs)

Environment   Protection   Industrial Permit   Outfalls   Feature 11

Outfall 03A160 for the TA-35-124/595 National High Magnetic Field Laboratory (NHMFL) Cooling Tower

Description: A cooling tower provides water cooling to equipment and systems at the National High Magnetic Field Laboratory. The water is treated using a corrosion inhibitor then batched into two storage tanks. Water from these tanks is treated to remove copper prior to discharge into Ten-Site Canyon. Discharged water meets all regulatory standards.

Permitted Discharge: Cooling tower blow-down

Receiving Stream: Ephemeral tributary of Ten Site Canyon, Segment Number 20.6.4.128

Constituent Monitoring: Flow, TSS, Phosphorous, Metals, pH and WET

Monitoring Frequency: Variable 1/day, 1/week, 1/month1/quarter

Reporting Frequency: Monthly and quarterly Discharge Monitoring Reports (DMRs)